Economic running costs
Capacity,0-100% adjustment When the gas consumption is reduced, the capacity decreases, following motor current is also reduced, air compressor is running without capacity, if this status keeps for a long time, compressor automatically shut down. While air consumption increases, compressors recovers. Energy-saving effect is optimal.
Good environmental adaptability
Extraordinary cooling system design, especially for the Asian high-temperature, high humidity environment. Excellent vibration isolation and noise reduction measures, so that the installation of our screw compressor no need for a dedicated basis, only to leave a minimum ventilation and maintenance space, you can settle your compressor.
Screw rotor profile design features:
First, the curved face of the rotors engaged fully, thus contributing to the formation of a hydrodynamic lubrication film, reducing the contact zone of the lateral leakage, improve compressor efficiency; as well as to improve the processing, test performance of the rotor.
Second, using the design ideas of bigger rotor, bigger bearing, low-speed ", speed lower than other brands up to 30 ~ 50%, this could reduce noise and vibration, reducing the compressed air temperature and improve the rigidity of rotor and prolong its life, reduce sensitivity to the impurity and the oil carbide.
Fourth, fully meet or exceed the national standard ISO19153-2003 "air compressors energy efficiency limit !
185KW air cooling compressor parameters
ITEM | UNIT | MODEL | ||||
LGCD-30/8 | LGCD-25/10 | LGCD-21/13 | ||||
Discharge capacity | m3/min | 27 | 23 | 20 | ||
Working pressure | MPa | 0.8 | 1.0 | 1.3 | ||
Cooling style | Air cooling | |||||
Working style | one stage, continuous working | |||||
Driven method | Direct driven | |||||
Inlet status | Temperature | ℃ | ≤40 | |||
Pressure | MPa | Atmospheric pressure | ||||
Relative humidity | ≤100% | |||||
Noise | dB(A) | ≤83 | ||||
Oil content | ppm | ≤2 | ||||
Drive rotor speed | rpm | 2974 | ||||
Dust particle size | μm | 1μm | ||||
Cooler outlet temperature | ℃ | Ambient temperature+10 | ||||
Cooling air flow | m3/min | 700 | ||||
Displacement control mode | Load/empty + stop for too long empty status | |||||
Safety valve set pressure | MPa | 0.88 | 1.1 | 1.43 | ||
Lubricating oil volume | L | 120 | ||||
Lubricating oil brand | ROTORCOMP | |||||
Air outlet connection size | DN65 | |||||
Drain connection size | G1 | |||||
Dimension | L | mm | 2650 | |||
W | mm | 1650 | ||||
H | mm | 1800 | ||||
Net Weight | kg | 3150 | ||||
Motor | Type | Y2315L1-2 | ||||
Rating | rpm | 2974 | ||||
Power | KW | 185 | ||||
Service coefficient | 1.2 | |||||
Degree of protection | IP55 | |||||
Insulation class | FB | |||||
Startup mode | Reduced voltage | |||||
Voltage | V | 380 | ||||
Frequency | Hz | 50 | ||||
Rated current | A | 280 | ||||
Weight of motor | kg | 1080 |
Contact Us at Any Time